Technical Specifications - MultiCom 302 Protocol Converter
Overview
- Protocol converter card for Riello UPS and Transfer Switches.
- Enables monitoring and control via Modbus (RTU) / Jbus and proprietary protocols.
- Provides two serial communication ports:
- SERIAL 1: RS232 (for proprietary GPSER protocol)
- SERIAL 2: RS485 Half-Duplex or RS232 (Modbus/Jbus or GPSER)
Communication Features
- Baud Rate Support: 1200-57600 bps (configurable via DIP switch or MultiSetup software).
- Parity Options: None, Even, Odd.
- Stop Bits: 1 or 2.
- LEDs indicate serial activity (Green for SERIAL 1, Yellow for SERIAL 2).
- Supports Modbus function codes:
- 0x01, 0x02 (Bit Reading)
- 0x03, 0x04 (Register Reading)
- 0x06, 0x10 (Register Writing)
Installation & Configuration
- Plug into UPS communication slot (hot-swappable).
- DIP switches available for setting:
- RS232/RS485 mode
- Device Modbus address (1-31 via DIP, 32+ via software)
- Baud rate
- RS485 bus terminal resistor (120Ω option)
Monitoring Capabilities
- Real-time UPS status, measurements (e.g., voltages, frequencies, load percentages, battery data).
- Alarm monitoring (e.g., low battery, overload, UPS failure).
- Commands support for shutdown, battery testing, and diagnostics.
Environmental
- Indoor installation only (clean, dry environment).
- Operating Temperature: 0°C to 40°C.
- Relative Humidity: <90% RH (non-condensing).
CertificationsISO 9001, ISO 14001, OHSAS 18001, CE
Download Catalog : DATCONX0Y23BREN-2