EPOWER 10-160KVA

SKU : SKU20
EPower UPS is a True Online 3-phase system supporting unbalanced loads and parallel operation up to 6 units. Generator-compatible with ECO Mode, smart battery charging, SNMP support. Ideal for business and industry.

Product Description

Key Technical Features - EPower UPS (10-160KVA)

  • True Online Double Conversion: Provides clean, stable power with full protection from sags, surges, and blackouts
  • Dual DSP Control: Enhances system stability and operational precision
  • High Power Factor (0.9): Full load support with reduced energy loss
  • N+X Parallel Redundancy: Scalable up to 6 units for reliability and flexibility
  • ECO Mode Efficiency up to 98%: Optimizes energy usage and lowers operational cost
  • Advanced Battery Management: Prolongs battery life and improves charging efficiency
  • Cold Start Function: Allows battery-mode startup without utility power
  • Generator Compatible: Ensures smooth operation with backup generators
  • LBS Synchronization: Synchronizes output of multiple UPS systems
  • Comprehensive Protection: Overload, short circuit, overvoltage, undervoltage
  • Intelligent Fan Speed Control: Reduces noise and extends component life
  • EPO (Emergency Power Off): For safety-critical shutdown
  • Multiple Communication Interfaces: RS232, RS485, MODBUS, Dry Contact, SNMP (optional)
  • Certified: TIS 1291-2553 (1), TIS 1291-2553 (2), TIS 1291-2555 (3), ISO 9001, ISO 14001, OHSAS 18001, CE

Technical Specifications:

  • Power Ratings:
    • 10KVA (9KW), 20KVA (18KW), 30KVA (27KW),
    • 40KVA (36KW), 60KVA (54KW), 80KVA (72KW),
    • 100KVA (90KW), 120KVA (108KW), 160KVA (144KW)
  • Input:
    • Voltage: 380/400/415V ±25%
    • Frequency: 50/60Hz ±10% (adjustable)
    • Power Factor: ≥0.97
  • Output:
    • Voltage: 380/400/415V ±1%
    • Frequency: 50/60Hz ±0.2% (Battery Mode)
    • Power Factor: 0.9
    • THD: ≤3% (linear load)
    • Crest Factor: 3:1
    • Overload: 125% (10 min), 150% (1 min)
  • Battery:
    • DC Voltage: 384V (360-384V optional)
    • Charging Current: Adjustable 10-40A
    • Management: Intelligent battery management system
  • Special Features:
    • Fault Trace Management (FTM)
    • Battery Self-Test Function
    • ECO Mode up to 98% efficiency
    • Optional Bypass Isolation Transformer
Communication & Monitoring:
  • Ports: RS232, RS485, MODBUS, Dry Contact, SNMP (optional)
  • Display: LCD Touchscreen (4.7" / 7" optional)
Environmental:
  • Operating Temp: 0-40°C
  • Noise Level: <65 dB @ 1 meter
Recommended Applications:
  • Data centers and critical IT environments
  • Industrial machinery and factory operations
  • Network and telecom systems
  • Large-scale businesses and enterprises

Download Catalog : EPower_10-160KVA Catalog
 


Ratings & Reviews